XM3.1-905-HPL
Power Supply Events
 
 

Alarms
 

Battery
 

Displayed time zone:
<<Prev 1 2 3 4 5 6 7 8 Next>>
Power Supply Events
  Time Event Description
155 2021-06-01 11:02:03 202B ALARM CLEARED :XM3-1 Comms Card Alarm=OK
154 2021-06-01 11:01:32 202F WARNING :XM3-1 Comms Card Alarm=ALARM
153 2021-05-26 19:07:25 202B ALARM CLEARED :XM3-1 INPUT FAIL ALARM=OK
152 2021-05-26 19:07:19 202A MINOR ALARM :XM3-1 INPUT FAIL ALARM=ALARM
151 2021-05-12 13:48:30 202B ALARM CLEARED :XM3-1 APP CLOCK NOT SET=0
150 2021-04-25 10:56:08 202B ALARM CLEARED :XM3-1 INPUT FAIL ALARM=OK
149 2021-04-25 10:56:02 202A MINOR ALARM :XM3-1 INPUT FAIL ALARM=ALARM
148 2021-04-19 11:16:44 200A TIME SET 15:15:40 04/19/21
147 2021-04-19 11:16:44 202B ALARM CLEARED :XM3-1 APP CLOCK NOT SET=0
146 2021-04-16 18:15:16 202B ALARM CLEARED :XM3-1 NO BATTERIES =OK
145 2021-04-16 18:15:07 2029 MAJOR ALARM :XM3-1 NO BATTERIES =NO BATT
144 2021-04-16 18:06:16 202B ALARM CLEARED :XM3-1 NO BATTERIES =OK
143 2021-04-16 18:06:07 2029 MAJOR ALARM :XM3-1 NO BATTERIES =NO BATT
142 2021-03-30 08:18:33 202B <1>ALARM CLEARED :XM3-1 INPUT FAIL ALARM=OK
141 2021-03-30 08:18:32 202A <1>MINOR ALARM :XM3-1 INPUT FAIL ALARM=ALARM
140 2021-03-29 10:09:40 202B ALARM CLEARED :XM3-1 INPUT FAIL ALARM=OK
139 2021-03-29 10:09:34 202A MINOR ALARM :XM3-1 INPUT FAIL ALARM=ALARM
138 2021-03-29 09:50:35 202B ALARM CLEARED :XM3-1 INPUT FAIL ALARM=OK
137 2021-03-29 09:50:28 202A MINOR ALARM :XM3-1 INPUT FAIL ALARM=ALARM
136 2021-03-17 08:18:18 202B <5>ALARM CLEARED :XM3-1 NO BATTERIES =OK
135 2021-03-17 08:18:17 2029 <5>MAJOR ALARM :XM3-1 NO BATTERIES =NO BATT
134 2021-03-16 17:35:37 202B ALARM CLEARED :XM3-1 NO BATTERIES =OK
133 2021-03-16 17:35:29 2029 MAJOR ALARM :XM3-1 NO BATTERIES =NO BATT
132 2021-03-16 17:28:45 202B ALARM CLEARED :XM3-1 NO BATTERIES =OK
131 2021-03-16 17:28:37 2029 MAJOR ALARM :XM3-1 NO BATTERIES =NO BATT
130 2021-03-04 08:18:03 202B <8>ALARM CLEARED :XM3-1 NO BATTERIES =OK
129 2021-03-04 08:18:02 2029 <8>MAJOR ALARM :XM3-1 NO BATTERIES =NO BATT
128 2021-03-03 09:59:02 202B ALARM CLEARED :XM3-1 NO BATTERIES =OK
127 2021-03-03 09:58:54 2029 MAJOR ALARM :XM3-1 NO BATTERIES =NO BATT
126 2021-03-03 09:45:58 202B ALARM CLEARED :XM3-1 NO BATTERIES =OK
125 2021-03-03 09:45:50 2029 MAJOR ALARM :XM3-1 NO BATTERIES =NO BATT
124 2021-03-03 08:21:29 200A TIME SET 12:20:23 03/03/21
123 2021-03-03 08:21:29 202B ALARM CLEARED :XM3-1 APP CLOCK NOT SET=0
122 2021-03-02 04:29:23 202B ALARM CLEARED :XM3-1 NO BATTERIES =OK
121 2021-03-02 04:29:14 2029 MAJOR ALARM :XM3-1 NO BATTERIES =NO BATT
120 2021-03-02 04:24:47 202B ALARM CLEARED :XM3-1 INPUT FAIL ALARM=OK
119 2021-03-02 04:24:38 202A MINOR ALARM :XM3-1 INPUT FAIL ALARM=ALARM
118 2021-03-02 02:46:24 202B ALARM CLEARED :XM3-1 INPUT FAIL ALARM=OK
117 2021-03-02 02:46:12 202A MINOR ALARM :XM3-1 INPUT FAIL ALARM=ALARM
116 2021-02-16 11:49:23 202B ALARM CLEARED :XM3-1 NO BATTERIES =OK
115 2021-02-16 11:49:15 2029 MAJOR ALARM :XM3-1 NO BATTERIES =NO BATT
114 2021-02-16 11:44:39 202B ALARM CLEARED :XM3-1 INPUT FAIL ALARM=OK
113 2021-02-16 11:44:33 202A MINOR ALARM :XM3-1 INPUT FAIL ALARM=ALARM
112 2021-02-16 10:30:43 202B ALARM CLEARED :XM3-1 INPUT FAIL ALARM=OK
111 2021-02-16 10:30:36 202A MINOR ALARM :XM3-1 INPUT FAIL ALARM=ALARM
110 2021-02-14 11:16:10 202B <3>ALARM CLEARED :XM3-1 NO BATTERIES =OK
109 2021-02-14 11:16:09 2029 <3>MAJOR ALARM :XM3-1 NO BATTERIES =NO BATT
108 2021-02-13 17:30:32 202B ALARM CLEARED :XM3-1 NO BATTERIES =OK
107 2021-02-13 17:30:24 2029 MAJOR ALARM :XM3-1 NO BATTERIES =NO BATT
106 2021-02-13 17:20:43 202B ALARM CLEARED :XM3-1 NO BATTERIES =OK
105 2021-02-13 17:20:34 2029 MAJOR ALARM :XM3-1 NO BATTERIES =NO BATT
104 2021-02-03 11:15:57 202B <5>ALARM CLEARED :XM3-1 NO BATTERIES =OK
103 2021-02-03 11:15:56 2029 <5>MAJOR ALARM :XM3-1 NO BATTERIES =NO BATT
102 2021-02-03 09:45:21 202B ALARM CLEARED :XM3-1 NO BATTERIES =OK
101 2021-02-03 09:45:13 2029 MAJOR ALARM :XM3-1 NO BATTERIES =NO BATT
100 2021-02-03 09:26:57 202B ALARM CLEARED :XM3-1 NO BATTERIES =OK
99 2021-02-03 09:26:49 2029 MAJOR ALARM :XM3-1 NO BATTERIES =NO BATT
98 2021-01-19 11:18:24 202B ALARM CLEARED :XM3-1 APP CLOCK NOT SET=0
97 2021-01-16 15:32:34 202B <4>ALARM CLEARED :XM3-1 NO BATTERIES =OK
96 2021-01-16 15:32:33 2029 <4>MAJOR ALARM :XM3-1 NO BATTERIES =NO BATT
95 2021-01-15 16:09:20 202B ALARM CLEARED :XM3-1 Comms Card Alarm=OK
94 2021-01-15 16:07:17 202F WARNING :XM3-1 Comms Card Alarm=ALARM
93 2021-01-15 15:46:21 202B ALARM CLEARED :XM3-1 NO BATTERIES =OK
92 2021-01-15 15:45:21 2029 MAJOR ALARM :XM3-1 NO BATTERIES =NO BATT
91 2021-01-15 15:44:49 202B ALARM CLEARED :XM3-1 NO BATTERIES =OK
90 2021-01-15 15:43:13 202B ALARM CLEARED :XM3-1 BATT TEMP PROBE =OK
89 2021-01-15 15:35:48 2035 CM IP CHANGED TO 10.68.59.75
88 2020-11-17 11:58:16 200A TIME SET 19:35:35 01/15/21
87 2020-11-17 11:58:16 202B ALARM CLEARED :XM3-1 APP CLOCK NOT SET=0
86 2020-11-17 11:55:14 2029 MAJOR ALARM :XM3-1 NO BATTERIES =NO BATT
85 2020-11-17 11:55:14 202A MINOR ALARM :XM3-1 BATT TEMP PROBE =ALARM
84 2020-11-17 11:55:01 2029 MAJOR ALARM :XM3-1 NO BATTERIES =NO BATT
83 2020-11-17 11:55:01 202A MINOR ALARM :XM3-1 BATT TEMP PROBE =ALARM
82 2020-11-17 11:54:48 2029 MAJOR ALARM :XM3-1 NO BATTERIES =NO BATT
81 2020-11-17 11:54:48 202A MINOR ALARM :XM3-1 BATT TEMP PROBE =ALARM
80 2020-11-17 11:54:35 2029 MAJOR ALARM :XM3-1 NO BATTERIES =NO BATT
79 2020-11-17 11:54:27 202A MINOR ALARM :XM3-1 BATT TEMP PROBE =ALARM
78 2020-11-17 11:54:22 2029 MAJOR ALARM :XM3-1 NO BATTERIES =NO BATT
77 2020-11-17 11:54:22 202A MINOR ALARM :XM3-1 BATT TEMP PROBE =ALARM
76 2020-11-17 10:22:10 2030 INFO :XM3-1 TAMPER DETECTED =1
75 2020-11-17 10:22:05 202A MINOR ALARM :XM3-1 BATT TEMP PROBE =ALARM
74 2020-11-17 04:30:34 2038 ALARM CLEARED :XM3-1 ACTIVE DROP =0 NEW: 331W, OLD: 329W
73 2020-11-16 22:30:32 2001 02:15:12 11/17/20920s UTILITY EVENT: OUTAGE
72 2020-11-16 21:03:07 202B ALARM CLEARED :XM3-1 OUTPUT OVERLOAD =OK
71 2020-11-16 20:29:51 2029 MAJOR ALARM :XM3-1 OUTPUT OVERLOAD =ALARM
70 2020-11-16 19:55:37 202B ALARM CLEARED :XM3-1 OUTPUT OVERLOAD =OK
69 2020-11-16 19:21:46 2029 MAJOR ALARM :XM3-1 OUTPUT OVERLOAD =ALARM
68 2020-11-16 19:00:18 2001 22:53:55 11/16/20383s UTILITY EVENT: OUTAGE
67 2020-11-16 18:29:20 2001 22:28:18 11/16/20 62s UTILITY EVENT: OUTAGE
66 2020-11-16 18:22:15 2001 22:21:12 11/16/20 63s UTILITY EVENT: OUTAGE
65 2020-11-16 18:21:13 2002 22:18:06 11/16/20187s UTILITY EVENT: SAG
64 2020-11-16 18:15:04 2001 22:13:50 11/16/20 74s UTILITY EVENT: OUTAGE
63 2020-11-16 18:07:36 201A ALARM CLEARED :XM3-1 OUTPUT FAIL ALARM=OK
62 2020-11-16 18:07:14 201A MAJOR ALARM :XM3-1 OUTPUT FAIL ALARM=ALARM
61 2020-11-16 18:07:07 2001 22:06:29 11/16/20 38s UTILITY EVENT: OUTAGE
60 2020-11-16 18:05:59 202B ALARM CLEARED :XM3-1 Low Batt Disconnect=OK
59 2020-11-16 18:03:25 202C ALARM CLEARED :XM3-1 INPUT CURRENT LIMIT=OK 4A
58 2020-11-16 18:03:24 202C MINOR ALARM :XM3-1 INPUT CURRENT LIMIT=ALARM 9A
57 2020-11-16 18:00:31 2029 MAJOR ALARM :XM3-1 Low Batt Disconnect=STRING
56 2020-11-16 18:00:23 2001 21:59:15 11/16/20 68s UTILITY EVENT: OUTAGE
<<Prev 1 2 3 4 5 6 7 8 Next>>

 
Copyright © 2020 Alpha Technologies Services, Inc. - an EnerSys company
www.alpha.com   |   www.enersys.com