XM3.1-905-HPL
Power Supply
 
 

Alarms
 

Battery
 

Power Supply
Model ALPHA/XM3.1-905-HPL
Firmware V0.03.4A
Major Alarm OK
Minor Alarm OK
Operational Mode Line
Charger Mode Float
Tamper Closed
Power Supply Language English
Power Supply Priority Normal
Input
AC Line Mode OK
Voltage 120.07 V
Current 3.71 A
Power 396 W
Frequency 60 Hz
Tap Status Normal
Frequency Range 3.00 Hz
Current Limit 7.00 A
Input Power Consumption 11,324 Wh
Output
Voltage 87.83 V
Power 324 W
Apparent Power 383.81 VA
Frequency 60.06 Hz
Percent Load 87.40 %
Output Setting 90 V
Output Regulation Fine
Over-current Tolerance 3.000 sec
Retry Delay 60 sec
Retry Limit 20
Active Drop Alarm OK
Active Drop Threshold 50 W
Current 4.37 A
Inverter
Inverter Status Off
End of Discharge Type String
End of Discharge Level 1.75 V/cell
Reduced Peak Mode Disable
Total Standby Events 221
Time Since Last Standby Event 250d 15h:43m
Time in Last Standby Event 0d 1h:17m
Total Time in Standby 1,695 min
Standby Events Since Reset 131
Time in Standby Since Reset 984 min
Time Since Reset 1,698 day(s)
Total Run Time 1,698 day(s)
Total Downtime 14d 7h:57m
Oil Cap Lifespan Consumed 33.1 %
Self Test
Deep Discharge Cycle Timed
Test Countdown 23 day(s)
Test Duration 10 min
Test Interval 30 day(s)
Test Inhibit No

 
Copyright © 2020 Alpha Technologies Services, Inc. - an EnerSys company