XM3.1-905-HPL
Power Supply
 
 

Alarms
 

Battery
 

Power Supply
Model ALPHA/XM3.1-905-HPL
Firmware V0.03.4A
Major Alarm OK
Minor Alarm OK
Operational Mode Line
Charger Mode Float
Tamper Closed
Power Supply Language English
Power Supply Priority Normal
Input
AC Line Mode OK
Voltage 121.01 V
Current 3.70 A
Power 399 W
Frequency 60 Hz
Tap Status Normal
Frequency Range 3.00 Hz
Current Limit 7.00 A
Input Power Consumption 3,376 Wh
Output
Voltage 88.23 V
Power 325 W
Apparent Power 386.44 VA
Frequency 60.06 Hz
Percent Load 87.60 %
Output Setting 90 V
Output Regulation Fine
Over-current Tolerance 3.000 sec
Retry Delay 60 sec
Retry Limit 20
Active Drop Alarm OK
Active Drop Threshold 50 W
Current 4.38 A
Inverter
Inverter Status Off
End of Discharge Type String
End of Discharge Level 1.75 V/cell
Reduced Peak Mode Disable
Total Standby Events 213
Time Since Last Standby Event 133d 0h:04m
Time in Last Standby Event 0d 1h:17m
Total Time in Standby 1,655 min
Standby Events Since Reset 127
Time in Standby Since Reset 984 min
Time Since Reset 1,580 day(s)
Total Run Time 1,580 day(s)
Total Downtime 14d 7h:57m
Oil Cap Lifespan Consumed 29.7 %
Self Test
Deep Discharge Cycle Timed
Test Countdown 17 day(s)
Test Duration 10 min
Test Interval 30 day(s)
Test Inhibit No

 
Copyright © 2020 Alpha Technologies Services, Inc. - an EnerSys company
www.alpha.com   |   www.enersys.com